What causes the high-pressure failure of your water chiller machine? How to solve it?

 The high-pressure failure of the chiller means that the compressor discharge pressure is too high, which causes the high-pressure protection relay to operate. The compressor discharge pressure reflects the condensing pressure, the normal value should be 1.4~1.8MPa, and the protection value setting is recommended not to exceed 2.0MPa. Because the long-term pressure is too high, it will cause the compressor to run too much current, easily burn the motor, and cause damage to the compressor. So what is the main cause of high pressure failure? How to solve it?


water cooled chiller system


1. Excessive refrigerant charge. This situation generally occurs after maintenance, and it is manifested as high suction and discharge pressure and balance pressure, and the compressor operating current is also high.


Solution: The refrigerant should be discharged according to the suction and discharge pressure and the balance pressure and the operating current under the rated conditions until it is normal.


2. The cooling water temperature is too high and the condensing effect is poor. The rated working conditions of the cooling water required by the chiller are between 30 and 35. High water temperature and poor heat dissipation will inevitably lead to high condensing pressure. This phenomenon often occurs in high temperature seasons.


Solution: The reason for the high water temperature may be the failure of the cooling tower, such as the fan is not turned on or even reversed, the water distributor does not turn, it is manifested as the cooling water temperature is very high, and it rises rapidly; the outside temperature is high, the water path is short, and it can be circulated In this case, the cooling water temperature is generally maintained at a relatively high level, which can be solved by increasing the storage tank.


3. The cooling water flow is insufficient, and the rated water flow cannot be reached. The main performance is that the pressure difference between the inlet and outlet water of the unit becomes smaller (compared with the pressure difference at the beginning of the system's operation), and the temperature difference becomes larger.


Solution: The pipeline filter is clogged or the selection is too fine, and the water permeability is limited. Choose a suitable filter and clean the filter regularly; or the water pump is small and does not match the system.


4. The condenser is fouled or blocked. Condensate water generally uses tap water, it is easy to scale when it is above 30, and because the cooling tower is open, it is directly exposed to the air, dust and foreign matter can easily enter the cooling water system, causing the condenser to be dirty and blocking, and the heat exchange area is small. The efficiency is low, and it also affects the water flow. The performance is that the pressure difference and temperature difference between the inlet and outlet water of the unit become larger, the upper and lower temperatures of the condenser are very high when the condenser is touched by hand, and the condenser outlet copper pipe is hot.


Solution: The unit should be backwashed regularly, and chemical cleaning and descaling should be carried out if necessary.


5. False alarms caused by electrical faults. Because the high-voltage protection relay is damp, poorly contacted or damaged, the unit electronic board is damp or damaged, and the communication failure causes a false alarm.


Solution: For this kind of false fault, the HP fault indicator on the electronic board is often off or slightly bright, and the manual reset of the high-pressure protection relay is invalid. The running current of the compressor is normal, and the suction and exhaust pressures are also normal.


6. The refrigerant is mixed with non-condensable gases such as air and nitrogen. There is air in the refrigeration system. In many cases, the pointer of the high-pressure meter will vibrate severely when there is a lot of air.


Solution: This situation generally occurs after maintenance, and the vacuum is not complete. It can be evacuated at the highest point of the condenser after shutdown or re-evacuated to add refrigerant.


If your water chiller machine has a high-pressure alarm, you can check according to the article. Or you can contact the water chiller factory to help you solve it. Need to know the details of our water chiller machine, please visit the products page.


评论

此博客中的热门博文

How to design a water chiller system with AHU for pharmaceutical factory workshop | Hstarschiller.com

  Nowadays, it’s become more and more aware of pharmaceutical enterprises to realize the significance of building an efficient and green to environment cooling system in the factory, because it can not only help the owner to save the running cost but also contribute to the society by reducing the emissions, especially for those developed countries . But how to design a simple but energy saving cooling system with clean workshop? Below we are going to give you a real case for your reference to help you understand well, especially for those are quite new to the water chiller system field. Firstly,this project has been done by  H.Stars Group  ,including the system design,equipment manufacturing and installation etc. Below is the detailed project overview to help you understand the owner’s requirement . Project address: one of the pharmaceutical factories located in China Project desire: Requesting a constant temperature with humidity for oral solid preparation workshop Proje...

How is the Refrigeration Industry Leading the Green Development with R404A

  As global environmental concerns continue to rise, the refrigeration industry is undergoing a significant transformation. Water-cooled low-temperature units exported overseas are now increasingly adopting the eco-friendly refrigerant R404A, leading the way in the industry's green development. Here's a deeper look into this trend. Why Is R404A Becoming the Preferred Refrigerant for  Water-Cooled Low-Temperature Units ? R404A is a blend of refrigerants that stands out due to its environmentally friendly properties. It is free from Ozone Depleting Potential (ODP) and has a relatively low Global Warming Potential (GWP), making it an ideal substitute for traditional refrigerants. This balance between high-performance cooling and environmental friendliness has made R404A especially popular in regions with strict environmental regulations, such as Europe and North America. Water-cooled low-temperature units exported to these areas are now commonly equipped with R404A to meet local ...

Where are water-cooled chillers used? What is a chiller used for?

  Water-cooled chiller   is a cooling water device that can provide constant temperature, constant current and constant pressure. A chiller is a machine that achieves refrigeration through vapor compression or absorption cycles. These liquids can flow through heat exchangers to cool the air or equipment. The industrial chiller can always output ice water with a lower temperature than the ambient temperature. It can be used wherever cooling is required, either direct cooling or indirect heat exchange. The main components of a water-cooled chiller are compressor, condenser, evaporator, water pump, and water tank. Chillers have a wide range of applications. The chiller can be used to cool the injection mold, improve the quality of plastic products, cool the vacuum coating, control the temperature of the vacuum coating machine, cool the food industry, fast cooling processing, chemical industry, effectively control the temperature of chemicals, cooling buildings, concrete fast Cool...