1.Components of Chilled Water Pump Head: Evaporator water resistance of the refrigeration unit: typically 5-7m water column (refer to product samples). Water resistance of end devices (air handling units, fan coils): usually 5-7m water column (refer to product samples). Resistance of components such as return water filters, two-way control valves: generally 3-5m water column. Water resistance of headers and manifolds: typically 3m water column. Friction and local resistance losses along the refrigeration system piping: typically 7-10m water column. In summary, the pump head for chilled water is in the range of 26-35m water column, usually around 32-36m water column. Note: Pump head calculation depends on specific refrigeration system conditions; avoid blindly applying empirical values. 2.Components of Cooling Water Pump Head: Condenser water resistance of the refrigeration unit: generally 5-7m water column (refer to product samples). Water pressure at cooling tower spray nozzles:
We provide one-stop solution to HVAC customers, specializing in R&D, production, design and installation. Main products: Air Cooled Chiller, Water Cooled Chiller, Industrial Chiller, Multi-function Chiller, Hot Water Unit, Heat Recovery Unit, Heat Pump Unit, Condensing Unit, Low Temperature Chiller, Shell and Tube Heat Exchanger, Air Handling Unit, Fan Coil Unit, Cooling Tower, etc.