跳至主要内容

How to design heating system for a pharmaceutical factory dormitory building | Hstarschiller.com

 As we know that the simplest way to build heating system for hot water for dormitory is adopting boiler with coal burning ,which will cause CO2 increase for the earth. Here is the good example how to design the heating system with energy saving heat pumps to protect the environment.


pharmaceutical factory dormitory building


The project is the central air conditioning project and hot water project of a pharmaceutical factory dormitory building, canteen. The dormitory building has a total air conditioning area of 5700 square meters, 200 people and the canteen area of 1044 square meters. In the original design institute scheme, 14 air source heat pump units are used in the dormitory building, 4 air source heat pump units are used in the canteen, and the machine rooms are located on the roof of each building. Our company has optimized the system design:
(1) The dormitory building and canteen are combined into one system
(2) The system adopts air source multi-functional unit.

Project requirements

Name

Area

Air conditioning cooling load

Air conditioning heat load

Hot water load

Dormitory building

5700m2

615kw

308kw

800kw

canteen

1044m2

185kw

96kw

\


Project design

1. Cold and heat source design
The system adopts two sets of R1234ze air source multi-functional units, with a total refrigerating capacity of 614kw and a total heating capacity of 652kw, which are used for cold and hot water of air conditioning in dormitory buildings, canteens and sanitary hot water in dormitory buildings
2、 Supply and return water temperature : 7 ℃ / 12 ℃ in summer and 45 ℃ / 40 ℃ in winter; Hot water 55 ℃ ;
3、 Water system design : The closed mechanical circulation system is adopted, and two vertical circulating water pumps (one for use and one for standby) are selected.



Project configuration

Equipment name

Cooling capacity

Power

Heating capacity

Power

Heat recovery

quantity

remark

Air source multifunctional machine

307kw

90kw

326kw

85kw

123kw

2unit


Benefit analysis

(1) The air source multi-functional unit is adopted for the combination of the system, and the initial investment cost can be reduced by 25% ~ 30% 。
(2) The heat recovery capacity of the unit is 123kw / set, and the unit produces 55 ℃ hot water per hour :M=Q/△T=123kw×1000×0.86/(55℃-15℃)=2.6m3/h, The two units produce a total of 5.2 tons of hot water per hour, saving at least 40% of the operation cost every year

Fuel mode

Fuel unit price

Theoretical calorific value

Comprehensive utilization rate

Hot water cost(RMB/T)

Maintenance cost(Ten thousand/yuan

Diesel boiler

6yuan/kg

10200kcal/kg

85%

27.6

6

Natural gas boiler

3.5yuan/m3

8600kcal/m3

75%

21.7

8

LPG boiler

5yuan/kg

10800kcal/kg

70%

26.5

7

Electric hot water boiler

1yuan/kwh

860kcal/kwh

90%

48.9

5


Heat recovery

--

----

--

0

0


Project advantages
(1) One machine with three functions and complete functions; Air conditioning and free domestic hot water are provided in summer, heating and domestic hot water are provided in winter, and domestic hot water is provided in transition seasons ;
(2) Microcomputer control, automatic switching between hot and cold working conditions ;
(3) Equipped with heat recovery, refrigeration and free sanitary hot water ;
(4) When the air conditioning of dormitory building and canteen is used in peak shift, the two systems are centralized into one system, which can reduce the load of equipment allocation, improve the utilization rate of equipment and reduce the initial investment cost ;
(5) The system is highly centralized, and one set of system can meet the needs of refrigeration, heating and hot water and reduce management costs ;
(6) The unit has compact structure, small floor area and simple installation; Reduce initial investment and equipment later maintenance costs
(7) Green energy saving R1234ze refrigerant , ODP is zero and GWP is almost 0.

Project system diagram

two vertical circulating water pumps Project system diagram


评论

此博客中的热门博文

Where are water-cooled chillers used? What is a chiller used for?

  Water-cooled chiller   is a cooling water device that can provide constant temperature, constant current and constant pressure. A chiller is a machine that achieves refrigeration through vapor compression or absorption cycles. These liquids can flow through heat exchangers to cool the air or equipment. The industrial chiller can always output ice water with a lower temperature than the ambient temperature. It can be used wherever cooling is required, either direct cooling or indirect heat exchange. The main components of a water-cooled chiller are compressor, condenser, evaporator, water pump, and water tank. Chillers have a wide range of applications. The chiller can be used to cool the injection mold, improve the quality of plastic products, cool the vacuum coating, control the temperature of the vacuum coating machine, cool the food industry, fast cooling processing, chemical industry, effectively control the temperature of chemicals, cooling buildings, concrete fast Cool...

Ways and solutions of noise produced by chillers - www.oumalchiller.com

  It is inevitable that the chiller will produce sound when it is working. For example, when the fan rotates, the fan blades rub against the air, it will produce sound. Normal sound is allowed. However, even the sophisticated refrigeration equipment will appear after a long period of use. Fault. Then, the editor of   Oumal Chiller   will take you to understand the causes and solutions of the noise produced by the chiller. First, find the reason from the parts that are easy to check and observe: 1. Are the anchor screws loose? The chiller is fixed on the ground. After running for a long time, the anchor bolts will be loose, and the chiller will be unstable, which will cause noise. This situation can be solved by replacing the anchor bolts, and vibration reduction can also be installed if conditions permit. The purpose is to make the chiller firmly fixed on the ground. 2. Whether the connecting pipeline is firm There are large and small pipes on the chiller, connecting the ...

How is the Refrigeration Industry Leading the Green Development with R404A

  As global environmental concerns continue to rise, the refrigeration industry is undergoing a significant transformation. Water-cooled low-temperature units exported overseas are now increasingly adopting the eco-friendly refrigerant R404A, leading the way in the industry's green development. Here's a deeper look into this trend. Why Is R404A Becoming the Preferred Refrigerant for  Water-Cooled Low-Temperature Units ? R404A is a blend of refrigerants that stands out due to its environmentally friendly properties. It is free from Ozone Depleting Potential (ODP) and has a relatively low Global Warming Potential (GWP), making it an ideal substitute for traditional refrigerants. This balance between high-performance cooling and environmental friendliness has made R404A especially popular in regions with strict environmental regulations, such as Europe and North America. Water-cooled low-temperature units exported to these areas are now commonly equipped with R404A to meet local ...