跳至主要内容

How to design heating system for a pharmaceutical factory dormitory building | Hstarschiller.com

 As we know that the simplest way to build heating system for hot water for dormitory is adopting boiler with coal burning ,which will cause CO2 increase for the earth. Here is the good example how to design the heating system with energy saving heat pumps to protect the environment.


pharmaceutical factory dormitory building


The project is the central air conditioning project and hot water project of a pharmaceutical factory dormitory building, canteen. The dormitory building has a total air conditioning area of 5700 square meters, 200 people and the canteen area of 1044 square meters. In the original design institute scheme, 14 air source heat pump units are used in the dormitory building, 4 air source heat pump units are used in the canteen, and the machine rooms are located on the roof of each building. Our company has optimized the system design:
(1) The dormitory building and canteen are combined into one system
(2) The system adopts air source multi-functional unit.

Project requirements

Name

Area

Air conditioning cooling load

Air conditioning heat load

Hot water load

Dormitory building

5700m2

615kw

308kw

800kw

canteen

1044m2

185kw

96kw

\


Project design

1. Cold and heat source design
The system adopts two sets of R1234ze air source multi-functional units, with a total refrigerating capacity of 614kw and a total heating capacity of 652kw, which are used for cold and hot water of air conditioning in dormitory buildings, canteens and sanitary hot water in dormitory buildings
2、 Supply and return water temperature : 7 ℃ / 12 ℃ in summer and 45 ℃ / 40 ℃ in winter; Hot water 55 ℃ ;
3、 Water system design : The closed mechanical circulation system is adopted, and two vertical circulating water pumps (one for use and one for standby) are selected.



Project configuration

Equipment name

Cooling capacity

Power

Heating capacity

Power

Heat recovery

quantity

remark

Air source multifunctional machine

307kw

90kw

326kw

85kw

123kw

2unit


Benefit analysis

(1) The air source multi-functional unit is adopted for the combination of the system, and the initial investment cost can be reduced by 25% ~ 30% 。
(2) The heat recovery capacity of the unit is 123kw / set, and the unit produces 55 ℃ hot water per hour :M=Q/△T=123kw×1000×0.86/(55℃-15℃)=2.6m3/h, The two units produce a total of 5.2 tons of hot water per hour, saving at least 40% of the operation cost every year

Fuel mode

Fuel unit price

Theoretical calorific value

Comprehensive utilization rate

Hot water cost(RMB/T)

Maintenance cost(Ten thousand/yuan

Diesel boiler

6yuan/kg

10200kcal/kg

85%

27.6

6

Natural gas boiler

3.5yuan/m3

8600kcal/m3

75%

21.7

8

LPG boiler

5yuan/kg

10800kcal/kg

70%

26.5

7

Electric hot water boiler

1yuan/kwh

860kcal/kwh

90%

48.9

5


Heat recovery

--

----

--

0

0


Project advantages
(1) One machine with three functions and complete functions; Air conditioning and free domestic hot water are provided in summer, heating and domestic hot water are provided in winter, and domestic hot water is provided in transition seasons ;
(2) Microcomputer control, automatic switching between hot and cold working conditions ;
(3) Equipped with heat recovery, refrigeration and free sanitary hot water ;
(4) When the air conditioning of dormitory building and canteen is used in peak shift, the two systems are centralized into one system, which can reduce the load of equipment allocation, improve the utilization rate of equipment and reduce the initial investment cost ;
(5) The system is highly centralized, and one set of system can meet the needs of refrigeration, heating and hot water and reduce management costs ;
(6) The unit has compact structure, small floor area and simple installation; Reduce initial investment and equipment later maintenance costs
(7) Green energy saving R1234ze refrigerant , ODP is zero and GWP is almost 0.

Project system diagram

two vertical circulating water pumps Project system diagram


评论

此博客中的热门博文

Avoid Downtime, Cut Costs: Smart Maintenance for Smarter Chillers

  Screw water-cooled chillers   typically operate around 3,000 hours per year, depending on China's climate and geographical conditions. Regular and scientific maintenance is crucial to ensure long-term, reliable operation, extend the lifespan, and reduce operating costs. Maintenance and Upkeep Preventive maintenance during operation and inspection involves creating annual and monthly maintenance plans based on actual operating conditions. Shutdown Procedures In winter, clean and dry the unit. Open the drain valve to empty the  shell-and-tube heat exchanger  to avoid freezing. The shutdown sequence is: chiller off - cooling tower fan off - cooling water pump off - chilled water pump off. Special attention to anti-freezing: 1. Drain the evaporator and condenser if the unit is outdoors below 0°C during standby. 2. Interlock the water flow switch with the unit to prevent freezing when the chilled water flow switch malfunctions. 3. Ensure water in the evaporator is flowi...

What are the differences between air-cooled chillers and water-cooled chillers | Oumalchiller.com

  We all know that according to different heat dissipation methods, chillers can be divided into air-cooled chillers and water-cooled chillers. What is the difference between air-cooled chillers and water-cooled chillers? ​ 1. The  air-cooled chiller  uses copper tubes and aluminum fins to dissipate heat from the condenser. A fan is required to blow the outdoor air through the heat exchange fins and take away the heat of the condenser, so the air-cooled chiller does not need to be connected to the cooling tower. But compared with water-cooled chillers, under the same power, air-cooled chillers have larger equipment size and higher noise. The condenser of water-cooled chillers exchanges heat with the cooling water from the cooling tower through the heat exchanger. The excess waste heat will be transported to the cooling tower through the cooling water loop and released into the atmosphere, or enter the water-water heat exchanger or soil heat exchange coil for storage. Ther...

What is difference between centrifugal chiller and screw chillers?

 Water Chillers are generally divided into the following categories: screw chillers, centrifugal chillers, water ring heat pump units, plate and tube evaporative condensing screw chillers, thermal storage air conditioners, etc. Screw chiller and centrifugal chiller are equipment that we often encounter. Below,  Oumal Refrigeration  will take you to understand the difference between centrifugal chiller and screw chiller? What is a  screw chiller ? The compressor adopts a screw type, hence the name screw chiller. The refrigerant coming out of the evaporator of the unit is a gas; after adiabatic compression by the compressor, it becomes a high-temperature and high-pressure state. The compressed gas refrigerant is isobarically cooled and condensed in the condenser. After condensation, it changes into liquid refrigerant, and then expands to low pressure through the throttle valve and becomes a gas-liquid mixture. The liquid refrigerant under low temperature and low pressu...