跳至主要内容

How to choose evaporator for cold storage?

 

Refrigeration Evaporators is a main heat exchanger used in the refrigeration system, which directly affects the efficiency of the refrigeration system. As we all know, the air cooler will use different fin spacing according to the required cold room temperature.Widely used fin spacing is 4mm, 4.2mm, 6.4 ~ 8mm,9.0mm, 10mm, 12mm. If the  cold storage temperature lower, the fin spacing larger. If the selection is unreasonable, the fins will frost quickly, and the passage of the wind will soon be blocked. It is difficult to cool the cold storage, and the compressor efficiency will reduce, resulting in increased power consumption in the refrigeration system.


According to engineering experience, generally 0 ℃ ~ 20 ℃ chiller room, such as workshop air conditioner, cool warehouse, cold storage room, fresh storage warehouse, air conditioning warehouse, ripening warehouse, etc., choose a fan with a blade distance of 4mm or 4.2mm; -16 ℃ ~ -25 ℃ cold freezer room, such as low-temperature freezing and refrigeration, low-temperature logistics warehouse, choose a fan with a blade distance of 6mm ~ 8mm; quick-freezing warehouse at -25 ℃ ~ -35 ℃, generally choose a fan with a blade distance of 9mm,10mm and 12mm


However, on some occasions, it is not possible to select the fin spacing of the cooler simply by temperature, such as quick pre-cooling of meat and vegetables, and acid discharge, although the temperature of the cold room is generally set above 0 ℃, but  the incoming temperature is higher and required quicker cooling, the humidity of the goods is high. If you choose a cooler with a fin space of 4mm ,4.2mm or 4.5mm, it is not suitable. You must use a cooler with a pitch of 8mm,9mm or even 10mm. Unless the fin will easily be defrosted.


Garlic and apples storage temperature is generally -2 ℃. For such fresh-keeping or modified atmosphere warehouses with a storage temperature lower than 0 ℃, evaporator fin space should not less than 8mm. To avoid power consumption and the blockage of the air duct caused by rapid frost.



评论

此博客中的热门博文

Avoid Downtime, Cut Costs: Smart Maintenance for Smarter Chillers

  Screw water-cooled chillers   typically operate around 3,000 hours per year, depending on China's climate and geographical conditions. Regular and scientific maintenance is crucial to ensure long-term, reliable operation, extend the lifespan, and reduce operating costs. Maintenance and Upkeep Preventive maintenance during operation and inspection involves creating annual and monthly maintenance plans based on actual operating conditions. Shutdown Procedures In winter, clean and dry the unit. Open the drain valve to empty the  shell-and-tube heat exchanger  to avoid freezing. The shutdown sequence is: chiller off - cooling tower fan off - cooling water pump off - chilled water pump off. Special attention to anti-freezing: 1. Drain the evaporator and condenser if the unit is outdoors below 0°C during standby. 2. Interlock the water flow switch with the unit to prevent freezing when the chilled water flow switch malfunctions. 3. Ensure water in the evaporator is flowi...

What Makes High-Temperature Heat Pump Units Essential for Modern Energy Use

  High-temperature heat pump units   have become essential to modern energy utilization technologies, finding widespread applications across various industries such as industrial, agricultural, and commercial sectors. These units' unique performance and advantages are key in driving energy transitions and achieving energy conservation and emission reductions. This blog will explore the working principles, application areas, technical features, and future trends of high-temperature heat pump units. How Do High-Temperature Heat Pump Units Work? High-temperature heat pump units operate based on the principle of the reverse Carnot cycle. They use a small amount of electrical or thermal energy to absorb heat from a low-temperature source and transfer it to a high-temperature source. The process involves four key stages: evaporation, compression, condensation, and expansion. During evaporation, the refrigerant absorbs heat from the low-temperature source and turns into a low-pressur...

What Are the Key Requirements for Flooded-Type Heat Exchangers in Air Suspension Chillers

  Air suspension chillers   are crucial in many industrial and commercial applications, and the flooded-type heat exchanger is one of the most important components of these systems. Understanding the requirements of the heat exchanger is essential to ensuring the air suspension units operate efficiently and remain stable. A flooded-type heat exchanger works by transferring heat between two fluids with different temperatures. In air suspension chillers, it helps regulate temperature, optimize energy use, and improve overall performance. For instance, it can transfer heat from high-temperature gases to low-temperature liquids, or vice versa. 1. Material Requirements 1.1 Corrosion Resistance In many industrial environments, fluids can be corrosive. For example, they may come into contact with acidic or alkaline substances. To withstand these conditions, the heat exchanger’s tubes and casing need to be made from corrosion-resistant materials, such as stainless steel. Stainless ste...