How to choose evaporator for cold storage?

 

Refrigeration Evaporators is a main heat exchanger used in the refrigeration system, which directly affects the efficiency of the refrigeration system. As we all know, the air cooler will use different fin spacing according to the required cold room temperature.Widely used fin spacing is 4mm, 4.2mm, 6.4 ~ 8mm,9.0mm, 10mm, 12mm. If the  cold storage temperature lower, the fin spacing larger. If the selection is unreasonable, the fins will frost quickly, and the passage of the wind will soon be blocked. It is difficult to cool the cold storage, and the compressor efficiency will reduce, resulting in increased power consumption in the refrigeration system.


According to engineering experience, generally 0 ℃ ~ 20 ℃ chiller room, such as workshop air conditioner, cool warehouse, cold storage room, fresh storage warehouse, air conditioning warehouse, ripening warehouse, etc., choose a fan with a blade distance of 4mm or 4.2mm; -16 ℃ ~ -25 ℃ cold freezer room, such as low-temperature freezing and refrigeration, low-temperature logistics warehouse, choose a fan with a blade distance of 6mm ~ 8mm; quick-freezing warehouse at -25 ℃ ~ -35 ℃, generally choose a fan with a blade distance of 9mm,10mm and 12mm


However, on some occasions, it is not possible to select the fin spacing of the cooler simply by temperature, such as quick pre-cooling of meat and vegetables, and acid discharge, although the temperature of the cold room is generally set above 0 ℃, but  the incoming temperature is higher and required quicker cooling, the humidity of the goods is high. If you choose a cooler with a fin space of 4mm ,4.2mm or 4.5mm, it is not suitable. You must use a cooler with a pitch of 8mm,9mm or even 10mm. Unless the fin will easily be defrosted.


Garlic and apples storage temperature is generally -2 ℃. For such fresh-keeping or modified atmosphere warehouses with a storage temperature lower than 0 ℃, evaporator fin space should not less than 8mm. To avoid power consumption and the blockage of the air duct caused by rapid frost.



评论

此博客中的热门博文

Avoid Downtime, Cut Costs: Smart Maintenance for Smarter Chillers

  Screw water-cooled chillers   typically operate around 3,000 hours per year, depending on China's climate and geographical conditions. Regular and scientific maintenance is crucial to ensure long-term, reliable operation, extend the lifespan, and reduce operating costs. Maintenance and Upkeep Preventive maintenance during operation and inspection involves creating annual and monthly maintenance plans based on actual operating conditions. Shutdown Procedures In winter, clean and dry the unit. Open the drain valve to empty the  shell-and-tube heat exchanger  to avoid freezing. The shutdown sequence is: chiller off - cooling tower fan off - cooling water pump off - chilled water pump off. Special attention to anti-freezing: 1. Drain the evaporator and condenser if the unit is outdoors below 0°C during standby. 2. Interlock the water flow switch with the unit to prevent freezing when the chilled water flow switch malfunctions. 3. Ensure water in the evaporator is flowi...

What are the differences between air-cooled chillers and water-cooled chillers | Oumalchiller.com

  We all know that according to different heat dissipation methods, chillers can be divided into air-cooled chillers and water-cooled chillers. What is the difference between air-cooled chillers and water-cooled chillers? ​ 1. The  air-cooled chiller  uses copper tubes and aluminum fins to dissipate heat from the condenser. A fan is required to blow the outdoor air through the heat exchange fins and take away the heat of the condenser, so the air-cooled chiller does not need to be connected to the cooling tower. But compared with water-cooled chillers, under the same power, air-cooled chillers have larger equipment size and higher noise. The condenser of water-cooled chillers exchanges heat with the cooling water from the cooling tower through the heat exchanger. The excess waste heat will be transported to the cooling tower through the cooling water loop and released into the atmosphere, or enter the water-water heat exchanger or soil heat exchange coil for storage. Ther...

What is difference between centrifugal chiller and screw chillers?

 Water Chillers are generally divided into the following categories: screw chillers, centrifugal chillers, water ring heat pump units, plate and tube evaporative condensing screw chillers, thermal storage air conditioners, etc. Screw chiller and centrifugal chiller are equipment that we often encounter. Below,  Oumal Refrigeration  will take you to understand the difference between centrifugal chiller and screw chiller? What is a  screw chiller ? The compressor adopts a screw type, hence the name screw chiller. The refrigerant coming out of the evaporator of the unit is a gas; after adiabatic compression by the compressor, it becomes a high-temperature and high-pressure state. The compressed gas refrigerant is isobarically cooled and condensed in the condenser. After condensation, it changes into liquid refrigerant, and then expands to low pressure through the throttle valve and becomes a gas-liquid mixture. The liquid refrigerant under low temperature and low pressu...