How to build a cost-saving cold room for Peanut Storage

 Peanut storage conditions have significant effects on overall quality. With H.Stars standards for roof pitch, ventilation and other building standards, farmer stock peanut warehouses or cold room are the best solution. Here are some suggestions on one of the type peanut cold storage.


Description of Peanut Cold Storage
1. Project details:
The specific parameters of the Peanut Cold Storage are as follows:
a. Cold storage size: 30m (length) × 25m (width) × 4.5m (height)
b. Cold storage temperature: 10 ℃
c. Cold storage goods: peanuts without shell

d: Storage capacity of cold storage: 1000Ton

cold room for Peanut Storage

Cold storage plants


2. After calculation, the chiller capacity of the cold storage is: 150kw

3. Refrigeration system description
(1). This project adopts: efficient refrigeration chilled water system.
a. The main refrigeration equipment of the high-efficiency chilled liquid refrigeration system is the water cooled chiller unit. After commissioning and testing in the factory, the whole chilled can be shipped to customer. The low failure rate also reduces the difficulty of on-site construction.
b. The refrigerant pipes of the high-efficiency refrigeration chilled water system are mainly concentrated in the chiller. There is no need to install refrigerant pipes on the site, reducing the risk of leakage, and it is easy to check even if a leakage occurs.
c. Because the high-efficiency refrigeration chilled water system has a good heat exchange effect of the chilled water and the state temperature, the air cooler in the warehouse can use air defrosting + electric heating defrosting, saving a lot of operating costs.(Electric heating defrosting is auxiliary, and it is turned on when the icing condition of the cooler is serious)
d. The chiller comes with three independent refrigeration systems, which can be used as backup systems for each other. The failure of any system will not affect the normal operation of other systems.
e. The failure rate of refrigeration chilled water system is low, and the service life is far beyond the fluorine refrigeration system.


(2) Equipment selection
a. Selection of chiller
Select a large temperature difference water-cooled three-parallel water chiller (design condition: -5℃ / 40℃, evaporator in/outlet temperature: 0℃/10℃,evaporative temperature: -5℃ )
Model: 40STD-FM600WDDH4, three independent refrigeration systems in parallel for one chiller (one of which is a standby system)
Total Cooling capacity 249kw, operating power: 77.4kw, cop: 3.2.
b. Selection of Cooling tower
The cooling tower uses a round type countercurrent cooling tower: the cooling water flow is 70m³/h, and the power is 1.5kw.
c. Selection of air cooler in the warehouse
In the warehouse uses six copper tube aluminum sheet air coolers: cooling capacity 40kw, water flow 3.5m³/ h, power 2.2kw
d. Selection of water pump
The chilled water pump use two vertical water pumps (one for use and one for standby): water flow 25m³/ h, head 32m, power 4kw
The cooling water pump uses two vertical water pumps (one for use and one for standby): water flow 22.3m³/ h, head 16m, power 2.2kw

Cold Storage Rooms

Water-cooled screw chiller


4. Description of other accessories
1). The selection and configuration of other accessories are based on relevant standards and design specifications.
2) All the valves, instruments and automatic control components of the refrigeration system adopt Freon special products.
3) The system pipes are all seamless steel pipes, and the cooling water pipes and defrosting drainage pipes are PVC pipes.
4) The pipeline insulation uses rubber and plastic insulation, which is convenient for construction operation and short in construction period.
5) Refrigerant: R134a, refrigeration oil: special oil for refrigeration unit.


Description of the cooling storage insulation

First. Overview of cold storage insulation
(1)External dimensions of cold storage: cold storage size: 30m (length) × 25m (width) × 4.5m (height)
(2)The cold storage wall panels and roof panels are made of polyurethane double-sided color steel plates, and the ground insulation is made of extruded plastic panels.
(3)The cold storage door adopts manual sliding door, the size is 1800mm * 2500mm * 75mm.


Second、The thickness of the cold storage insulation board
The top and outer wall of the refrigerator are made of 75mm, 0.426mm thick B2 grade double-sided color steel polyurethane board, external protection color steel plate, color steel plate thickness is 0.426mm, polyurethane bulk density is (40 ± 2) kg / m3. The ground is made of 100mm thick extruded plastic board, each extruded plastic board is 50mm thick, and the extruded plastic boards are spliced in the form of staggered overlap.

Cold

Storage

Category

Maintenance structure

Roof

Wallboard

Groud

Thicknessmm

Material

Thicknessmm

Material

Thicknessmm

Material

Cold storage

75

Double-sided

color steel

polyurethane board

75

Double-sided

color steel

polyurethane board

100

Extruded

board


Third、Technical Information of Insulation Board

1. Double-sided color steel polyurethane
1) The inner and outer panels are colored steel plates. The thickness of the color steel plate is 0.426mm. The color steel film coating is non-toxic, non-odorous, and corrosion-resistant, in line with food hygiene standards.

2) The bonding strength between the panel of the heat insulation board and the heat insulation material is ≥2.0kg / cm².
3) Overall performance of heat insulation board
a) The surface of the heat insulation board is kept flat and smooth, without warpage, scratches, bumps, uneven uneven defects.
b) There is no exposed insulation material on the joint surface of the heat insulation board, and the convex and concave defects on the joint surface are less than 1.5mm.
4) There are measures to prevent cold bridges where the thermal insulation wallboard meets the ground.
5) The glass seam between the heat insulation boards is sealed with glass glue, which meets the hygienic requirements and has good sealing performance, ensuring that the heat flow at the seam is not greater than twice the heat flow of the heat insulation board.
6) The connection structure between the heat insulation boards ensures that the pressure between the joints and the joints are firmly connected.
7) The tightness of the joint of the thermal insulation board of the library
a) The insulation material of the wallboard at the junction of the wallboard and the ground is in close contact with the insulation material in the floor, and it has reliable sealing and moisture-proof treatment.
b) The heat-insulating boards that make up the library body are integrated along its height, without horizontal mid-direction joints.
c) Tube wells and gaps between cold storage, cold storage and floors should be insulated and waterproofed.
d) Take measures to reduce the "cold bridge" effect on the lifting point structure of the ceiling of the reservoir, and seal the holes at the lifting points.

2. Extruded board

1) Extruded board has excellent thermal insulation, excellent high-strength compression resistance, high-quality water repellent and moisture resistance.
2) Process flow
Reinforced concrete structural layer → 1: 3 cement mortar leveling layer to ensure the level → polyethylene film → extruded plastic board

Insulation layer → polyethylene film → 1: 3 cement mortar leveling layer


System advantages:
1. The design of this system takes safety and stability as the main goal, and energy-saving and environmental protection as the auxiliary design concept. It chooses mature and low-failure refrigeration equipment to ensure the stable operation of the refrigeration system.
2.Refrigeration equipment chooses three parallel chillers with large temperature difference. One chiller is equipped with three independent refrigeration systems (one of which is a standby system), and by increasing the temperature difference between the in/outlet water(10℃), the water flow is reduced to save operating costs.
3. The condensing equipment uses a circular countercurrent cooling tower with reliable heat dissipation to ensure that the cooling effect in hot summer is not affected.
4. The refrigerating medium exchanges heat with the air temperature in the cold storage through the cooler, and the temperature of the cold storage is stable. Compared with the fluorine system, the frost of the cooler can be greatly reduced. The natural defrosting method can be adopted to save energy and protect the environment.(The electric melting frost is used as an auxiliary function configuration, usually not used only when the cooling fan has severe ice formation)

Cold Storage schematic diagram

cold storage room



If you are interested in chillers, you can contact us directly, email:maychow@hstars.com.cn

评论

此博客中的热门博文

Constant Temperature Swimming Pool Heat Pump Unit | Hstarschiller.com

  We all know that winter swimming has many advantages: 1. It can enhance cardiovascular function. 2. The stimulation of cold water can close the peripheral blood vessels, increase the blood supply of important organs such as heart, brain, liver and spleen, so that more oxygen can be delivered to brain cells in time, which is conducive to the elimination of nervous system fatigue. 3. The skin of those who insist on winter swimming is ruddy, shiny and elastic. And people also hope to enjoy the fun of swimming in winter, but not everyone can bear it.  Hstars group constant temperature swimming pool heat pump  can be a good solution. 1. Demand analysis of swimming pool with constant temperature Constant temperature swimming pool, also known as indoor constant temperature swimming pool; that is, the temperature of the water in the pool heating system is maintained at 26~28℃, which is suitable for the temperature of the human body. When the indoor swimming pool is designed, th...

The Role and Characteristics of Condenser in Refrigeration System

  The four major components of the refrigeration system are compressor, evaporator, condenser and throttling device. The role of the condenser in the refrigeration system is mainly to cool and liquefy the gaseous refrigerant in the high temperature and high pressure state discharged from the compressor, so as to meet the requirements of the circulating use of the refrigerant in the system. The selection of the temperature difference between the condensing temperature and the coolant inlet and outlet involves economic issues in the refrigeration system. Increasing the condensation temperature and reducing the temperature difference between the coolant inlet and outlet can increase the heat transfer temperature difference, reduce the required heat transfer area, and reduce the investment cost of heat exchange equipment. However, lowering the condensing temperature can reduce the power consumption of the refrigeration compressor. The greater the temperature difference between the cool...